ArchiStructura

Worked examples · No account needed

Every tool, worked end to end

Real inputs, every formula, substitution and result — each step linked to its Eurocode clause and explained in plain language. When you're ready, jump into the tool and run your own numbers.

01

Steel Beam Design

EN 1993-1-1 · Steel design

A rolled I-section floor beam: section classification, bending and shear resistance, and the deflection check — every substitution shown.

Bending 26% · shear 7% · deflection 40%

SectionIPE 300
Steel gradeS275 fy = 275 N/mm²
Support conditionSimply supported
Load typeUniform load (UDL)
Span L6 m
UDL w10 kN/m

Step-by-step working

01

Support reactions

EN 1990 · 6.2

RA = RB = w·L / 2

RA = 10 × 6 / 2

RA = RB = 30 kN

By symmetry and vertical equilibrium (ΣV = 0) each support carries half of the total load w·L.

02

Design bending moment

EN 1990 · 6.2

MEd = w·L² / 8 (midspan)

MEd = 10 × 6² / 8

MEd = 45 kNm

The moment diagram is parabolic with its peak at midspan — this is the value the cross-section design must resist.

03

Design shear force

EN 1990 · 6.2

VEd = w·L / 2 (supports)

VEd = 10 × 6 / 2

VEd = 30 kN

Shear is largest at the supports and zero at midspan — this value drives the shear design.

04

Maximum deflection

Euler–Bernoulli beam theory

δ = 5·w·L⁴ / (384·E·I)

δ = 5 × 10 × 6000⁴ / (384 × 210000 × 83560000)

δ = 9.62 mm

Instantaneous midspan deflection from elastic beam theory; the relevant material Eurocode (§7.2) sets the limit it is checked against.

05

Material factor, ε

EN 1993-1-1 · Table 5.2

ε = √(235 / fy)

ε = √(235 / 275)

ε = 0.924

Scales every classification limit with yield strength: the higher the grade, the stricter the c/t limits for the same class.

06

Web classification (bending)

EN 1993-1-1 · Table 5.2 (sheet 2)

c/t ≤ 72ε (Class 1) / 83ε (Class 2) / 124ε (Class 3)

c/t = hw/tw = 248.6/7.1 = 35.01 | 72ε = 66.6

Web is Class 1 (Plastic)

The web is an internal element in pure bending. Its slenderness decides whether it can sustain plastic rotation (Class 1), reach the plastic moment (Class 2), stay elastic (Class 3) or buckles locally (Class 4).

07

Flange classification (outstand in compression)

EN 1993-1-1 · Table 5.2 (sheet 3)

c/t ≤ 9ε / 10ε / 14ε, c = (b − 2r − tw)/2

c = (150 − 2×15 − 7.1)/2 = 56.5 mm | c/t = 5.28 | 9ε = 8.3

Flange is Class 1 (Plastic)

Each half-flange is an outstand element compressed by bending. The root radius r is excluded from the flat width c.

08

Overall cross-section class

EN 1993-1-1 · 5.5.2

Overall class = the more critical (higher) of web and flange class

Section is Class 1 (Plastic)

The section's class is set by its most slender part, and it decides whether the plastic modulus Wpl or only the elastic modulus Wel may be used in the bending check.

Plastic section properties (Wpl) may be used.

09

Bending resistance, Mc,Rd

EN 1993-1-1 · 6.2.5

Mc,Rd = Wpl·fy / γM0

Mc,Rd = 628,400 × 275 / 1.0

Mc,Rd = 172.81 kNm

Design bending resistance of the section. γM0 = 1.0 is the recommended partial factor for cross-section resistance — your National Annex may specify a different value.

10

Bending check

EN 1993-1-1 · 6.2.5

MEd / Mc,Rd ≤ 1.0

45 / 172.81

Utilization = 0.26 ✓

The ULS verification for bending: the design moment must not exceed the design resistance. A utilization above 1.0 means the section is overloaded.

11

Shear area, Av

EN 1993-1-1 · 6.2.6(3)

Av = A − 2b·tf + (tw + 2r)·tf (≥ η·hw·tw, η = 1.2)

Av = 5,381 − 2×150×10.7 + (7.1+2×15)×10.7

Av = 2568 mm²

Only the material near the web carries shear in an I-section. This rolled-section formula removes the flanges but adds back the material in the root radii; it may never be less than η·hw·tw.

12

Shear resistance, Vpl,Rd

EN 1993-1-1 · 6.2.6(2)

Vpl,Rd = Av·(fy/√3) / γM0

Vpl,Rd = 2568 × (275/√3) / 1.0

Vpl,Rd = 407.72 kN

Plastic shear resistance: yielding in shear at fy/√3 over the shear area. For slender webs the reduced value Vbw,Rd from EN 1993-1-5 applies instead.

13

Shear buckling susceptibility

EN 1993-1-1 · 6.2.6 (Eq 6.23)

Not susceptible if hw/tw ≤ 72ε/η

hw/tw = 35.01 vs 72ε/η = 55.5

Web is NOT susceptible to shear buckling.

Stocky webs (hw/tw below the limit) yield before they buckle, so the plastic shear resistance can be used without checking EN 1993-1-5.

VEd / Vpl,Rd ≤ 1.0

30 / 407.72

Utilization = 0.074 ✓

The ULS verification for shear. Where bending and shear interact heavily (VEd > 0.5·Vpl,Rd at the same point), the moment resistance must also be reduced per §6.2.8.

15

Deflection check (SLS)

EN 1993-1-1 · 7.2

δ ≤ L/250

δ = 9.62 mm vs limit = 24 mm

Utilization = 0.401 ✓

A serviceability (not safety) check: excessive deflection damages finishes and looks bad. The limit L/n is agreed for the project — EN 1993-1-1 §7.2 refers limits to the National Annex / client brief (L/250 is a common value for imposed load).

Try it yourself
02

Concrete Beam Design

EN 1992-1-1 · Concrete design

Flexural design of a rectangular RC section — singly or doubly reinforced — with the shear link check on top.

As 1476 mm² · 4 × φ25

Width b × depth h300 × 500 mm
Cover35 mm
Bar diameterφ25 mm
Concrete fck30 N/mm²
Steel fyk500 N/mm²
Design loadsMEd 250 kNm · VEd 150 kN

Step-by-step working

01

Effective depth, d

EN 1992-1-1 · 4.4.1

d = h − cover − φ/2

d = 500 − 35 − 25/2

d = 452.5 mm

Effective depth is measured to the centroid of the tension steel. The cover (nominal cover + allowance for deviation, §4.4.1) protects the bars against corrosion and fire.

02

Design yield strength of steel, fyd

EN 1992-1-1 · 3.2.7

fyd = fyk / 1.15

fyd = 500 / 1.15

fyd = 434.8 N/mm²

The characteristic yield strength fyk is divided by the partial factor γS = 1.15 (recommended value) to obtain the design strength used in all section checks.

03

Maximum moment for a singly reinforced section, MRdc

EN 1992-1-1 · 5.5(4) & 3.1.7

MRdc = 0.167 · fck · b · d²

MRdc = 0.167 × 30 × 300 × 453²

MRdc = 307.75 kNm

With the neutral axis at its ductility limit x/d = 0.45 (from §5.5, no redistribution) and the rectangular stress block of §3.1.7 (αcc = 0.85, γC = 1.5), the compressed concrete can carry at most this moment without compression steel.

04

Singly or doubly reinforced?

EN 1992-1-1 · 5.5

If MEd ≤ MRdc → singly reinforced. If MEd > MRdc → doubly reinforced.

MEd = 250 kNm vs MRdc = 307.75 kNm

Section is SINGLY reinforced — no compression steel needed.

Keeping x/d ≤ 0.45 guarantees the tension steel yields before the concrete crushes — a ductile failure with warning. If the moment exceeds MRdc, the excess is carried by compression steel instead of a deeper stress block.

z = (d/2) · [1 + √(1 − 3.53·MEd/(fck·b·d²))] (≤ 0.95d)

z = 389.6 mm

Distance between the tension steel and the centroid of the compression force. The closed form solves M = 0.8x·fcd·b·(d − 0.4x) of the rectangular stress block; the cap 0.95d is the code maximum lever arm.

06

Tension reinforcement, As

EN 1992-1-1 · 6.1

As = MEd / (fyd·z)

As = (250×10⁶) / (434.8 × 389.6)

As = 1476 mm²

Moment equilibrium of the internal couple: the steel force As·fyd acting through the lever arm z must balance the applied moment.

07

Suggested bar arrangement

EN 1992-1-1 · 8.2 & 9.2

Bars required = As / (area of one φ25 bar)

1476 / 491

Use 4 × φ25mm bars

Round up so the provided area is at least As, spread in at least two layers if needed. Detailing (spacing, anchorage, minimum steel per §9.2.1) must also be satisfied.

08

Concrete shear resistance without reinforcement, VRd,c

EN 1992-1-1 · 6.2.2 (Eqs 6.2a, 6.3N)

VRd,c = [0.12·k·(100ρ₁fck)^⅓]·bw·d (≥ vmin·bw·d)

k = 1.66, ρ₁ = 0.0109

VRd,c = 86.65 kN

Shear carried by the concrete alone: aggregate interlock and dowel action. k = 1 + √(200/d) ≤ 2 is a size effect, ρ1 (≤ 2%) is the tension steel ratio, and the floor value vmin = 0.035·k^1.5·√fck applies to lightly reinforced members.

09

Is shear reinforcement needed?

EN 1992-1-1 · 6.2.1

Shear reinforcement is required if VEd > VRd,c

VEd = 150 kN vs VRd,c = 86.65 kN

YES — links must be designed.

If the applied shear exceeds the concrete's capacity, designed links are required; where links are used at all, the minimum link area of §9.2.2 applies.

10

Design shear stress, vEd

EN 1992-1-1 · 6.2.3

vEd = VEd / (bw·z), z ≈ 0.9d

vEd = 1.23 N/mm²

Average shear stress over the effective web area bw·z — the working stress the truss model has to carry.

11

Concrete strut angle, θ

EN 1992-1-1 · 6.2.3

θ = 0.5·sin⁻¹[ vEd / (0.2·fck·(1 − fck/250)) ]

θ = 6.7° (cot θ = 2.5)

Strut inclination from the crushing limit of the concrete struts (VRd,max). Flatter struts (cot θ up to 2.5) need less steel but stress the struts more — the code limits cot θ to 1 ≤ cot θ ≤ 2.5.

12

Shear (link) reinforcement, Asw/s

EN 1992-1-1 · 6.2.3 (Eq 6.13)

Asw/s = vEd·bw / (fywd·cotθ)

Asw/s = 0.339 mm²/mm

From the variable-strut truss model: VRd,s = (Asw/s)·z·fywd·cotθ ≥ VEd. Choose a link diameter and spacing so the provided Asw/s per leg-set meets or exceeds this value.

Choose a link diameter and spacing so that Asw/s (for the chosen number of legs) meets or exceeds this value.

Try it yourself
03

Timber Beam Design

EN 1995-1-1 · Timber design

kmod and service-class factors, then bending, shear and both instantaneous and final deflection checks for a solid timber section.

Bending 20% · shear 10% · winst 21% · wfin 19%

Strength classC24 fm,k = 24 N/mm²
Service class / durationClass 2 · medium
Section b × h200 × 400 mm
Span L5 m
UDL w5 kN/m
Deflection limitswinst L/300 · wfin L/150

Step-by-step working

01

Modification factor, kmod

EN 1995-1-1 · Table 3.1

kmod = f(service class, load-duration class) [EC5 Table 3.1]

Service class 2, Medium-term load

kmod = 0.8

Timber strength depends on how long the load acts and how moist the wood is: short loads on dry timber can use more than the characteristic strength, while permanent loads in damp conditions must be reduced heavily.

02

Material partial factor, γM

EN 1995-1-1 · Table 2.3

γM = 1.30 (solid timber) / 1.25 (glulam)

γM = 1.3

Covers material variability and the effect of duration of load and moisture not already taken by kmod. These are the recommended values — several National Annexes (e.g. Denmark) specify different γM.

03

Deformation factor, kdef

EN 1995-1-1 · Table 3.2

kdef = f(service class) [EC5 Table 3.2]

kdef = 0.8

Creep factor: timber keeps deforming under sustained load, and the damper the environment (higher service class), the more creep.

04

Design bending strength, fm,d

EN 1995-1-1 · 2.4.1 (Eq 2.1)

fm,d = kmod·kh·fm,k / γM

fm,d = 0.8 × 1 × 24 / 1.3

fm,d = 14.77 N/mm²

EC5's basic recipe for every design strength: characteristic strength adjusted for duration and moisture (kmod), size (kh) and material safety (γM).

05

Section properties

Solid mechanics

W = b·h²/6, I = b·h³/12

b = — mm, h = — mm

W = 5333333 mm³, I = 1066666667 mm⁴

Elastic section modulus and second moment of area of the rectangular section — W converts moment into bending stress, I stiffens the beam against deflection.

06

Support reactions

EN 1990 · 6.2

RA = RB = w·L / 2

RA = 5 × 5 / 2

RA = RB = 12.5 kN

By symmetry and vertical equilibrium (ΣV = 0) each support carries half of the total load w·L.

07

Design bending moment

EN 1990 · 6.2

MEd = w·L² / 8 (midspan)

MEd = 5 × 5² / 8

MEd = 15.63 kNm

The moment diagram is parabolic with its peak at midspan — this is the value the cross-section design must resist.

08

Design shear force

EN 1990 · 6.2

VEd = w·L / 2 (supports)

VEd = 5 × 5 / 2

VEd = 12.5 kN

Shear is largest at the supports and zero at midspan — this value drives the shear design.

09

Maximum deflection

Euler–Bernoulli beam theory

δ = 5·w·L⁴ / (384·E·I)

δ = 5 × 5 × 5000⁴ / (384 × 11000 × 1066666667)

δ = 3.47 mm

Instantaneous midspan deflection from elastic beam theory; the relevant material Eurocode (§7.2) sets the limit it is checked against.

10

Bending stress check

EN 1995-1-1 · 6.1.6 (Eq 6.11)

σm,d = MEd/W ≤ fm,d

σm,d = 15.63×10⁶ / 5333333 = 2.93 N/mm² vs fm,d = 14.77 N/mm²

Utilization = 0.198 ✓

The ULS bending verification: the design bending stress from the elastic section modulus must not exceed the design bending strength.

11

Shear stress check

EN 1995-1-1 · 6.1.7 (Eq 6.13)

τd = 1.5·VEd/(b·h) ≤ fv,d, fv,d = kmod·fv,k/γM

τd = 1.5 × 12.5×10³ / (— × —) = 0.23 N/mm² vs fv,d = 2.46 N/mm²

Utilization = 0.095 ✓

The parabolic shear distribution is simplified to the average stress × 1.5. For members with cracks or notches at the support, §6.1.7 also requires an effective width kcr·b and load positioned within d from the support may be neglected.

12

Instantaneous deflection check

EN 1995-1-1 · 7.2

winst ≤ L/300

winst = 3.47 mm vs limit = 16.7 mm

Utilization = 0.208 ✓

Immediate deflection under the rare (characteristic) load combination, computed with the mean modulus E0,mean. The limiting L/n value comes from the National Annex (L/300 is a common requirement for timber).

13

Final deflection check

EN 1995-1-1 · 7.2 (Eq 7.2)

wfin = winst·(1 + kdef) ≤ L/150

wfin = 3.47 × (1 + 0.8) = 6.24 mm vs limit = 33.3 mm

Utilization = 0.187 ✓

Final deflection including creep: EC5 scales the instantaneous value by (1 + kdef), with the quasi-permanent load share contributing the creep part. The limit (commonly L/150) is set by the National Annex.

Try it yourself
04

Floor Joist Design

EN 1995-1-1 · Danish NA

Loads gathered from the floor build-up, then ULS bending and shear and the final SLS deflection for one joist — the NGH spreadsheet method.

ULS OK · SLS OK · u max 8.1 mm

Usage categoryA — A1 Rooms in residential buildings
Moveable partitions≤ 1 kN/m
JoistSawn 63x200 mm @ 0.5 m span 4.5 m
Timber qualityC18 service class 1
Acceptable deflectionL/500 9.0 mm
Design effectEd 3.43 kN/m² → 1.71 kN/m on the joist

Step-by-step working

01

Permanent loads gk

EN 1991-1-1

Σ gk = covering + joists + insulation + boarding + lining

Floor covering 0.08 + Joists 0.126 + Insulation 0.087 + Sec. spaced boarding 0.016 + Ceiling lining 0.117

Σ gk = 0.427 kN/m²

The joists enter as A·5 kN/m³ ÷ spacing; the insulation fills the joist depth at 0.5 kN/m³.

02

Variable loads qk

EN 1991-1-1 DK NA

qk = imposed load + moveable partitions

category A1 (Rooms in residential buildings): qk = 1.5 · partitions: 0.5

Σ qk = 2 kN/m²

03

Design uniform load and meter load

EN 1990 6.10

Ed = 1.0·gk + 1.5·qk → qjoist = Ed·spacing

1.0·0.427 + 1.5·2 = 3.43 kN/m² · × 0.5 m

Ed = 3.43 kN/m² → 1.71 kN/m on one joist

04

Design forces

Vd = ½·q·L · Md = q·L²/8

Vd = ½·1.71·4.5 · Md = 1.71·4.5²/8

Vd = 3.86 kN · Md = 4.34 kNm

05

Design bending strength

EN 1995-1-1 2.4.1

fmd, fvd from the quality and service class tables

C18 · service class 1 (Moisture ≤ 12 % — indoor.)

fmd = 10.7 N/mm² · fvd = 1.2 N/mm²

06

Bending check — ULS

EN 1995-1-1 6.1.6

Wness = Md/fmd ≤ Wy

4.34·1000/10.7 = 405 ·×10³ mm³ vs 420 ·×10³ mm³

OK — 420 ≥ 405 ×10³ mm³

07

Shear check — ULS

EN 1995-1-1 6.1.7

σvd = 1.5·Vd/A ≤ fvd

1.5·3.86·1000/12600 = 0.459 N/mm² vs fvd = 1.2

OK — 0.459 ≤ 1.2 N/mm²

08

Instantaneous and final deflection — SLS

EN 1995-1-1 7.2

uinst = 5·q·L⁴/(384·E·Iy) · ufin = uinst·(1 + ψ2·kdef)

frequent: 0.51 kN/m → 7.25 → 8.12 mm · quasi-perm.: 0.41 kN/m → 5.84 → 6.54 mm

governing u = 8.12 mm

E = 9000 N/mm², Iy = 42000·10³ mm⁴, kdef = 0.6 (class 1), ψ2 = 0.2.

09

Deflection limit

limit = L/500 (rounded up)

4.5·1000/500

OK — 9.0 mm ≥ 8.12 mm

Try it yourself
05

Snow Load on Roofs

EN 1991-1-3 · Danish NA

The characteristic roof snow load s = μi·Ce·Ct·sk,0 — shape coefficients, exposure and terrain value combined step by step.

s = 0.96 kN/m²

Roof shapeMono-pitch
Pitch30.0°
ExposureSheltered Ce = 1.20
Shape coefficientμ1 = 0.80
Terrain valuesk,0 = 1.00 kN/m² Danish annex

Step-by-step working

μ1 = 0.8 for α ≤ 30°; 0.8·(60 − α)/30 for 30° < α < 60°; 0 for α ≥ 60°

α = 30° → μ1 = 0.8

μ1 = 0.8

Snow slides less off shallow roofs: μ1 stays at 0.8 up to 30°, then falls linearly to zero at 60° — steeper roofs shed their snow.

02

Exposure coefficient Ce

DS/EN 1991-1-3 · Danish NA · 5.2(7)

Ce = 0.8 windswept · 1.0 normal · 1.2 sheltered

Sheltered → Ce = 1.2

Ce = 1.2

Windswept ground loses snow to the wind (load reduced); sheltered ground keeps it (load increased).

Ct = 1.0 (Danish national annex)

Ct = 1

Ct = 1

A warm roof melts its underside snow layer; the Danish annex fixes Ct at 1.0, so no reduction is taken here.

04

Characteristic ground snow load sk,0

DS/EN 1991-1-3 · Danish NA · terrain value

sk,0 from the national annex (terrain value)

sk,0 = 1 kN/m²

sk,0 = 1 kN/m²

The reference load on flat ground. The Danish annex takes sk,0 = 1.0 kN/m² for the whole country.

05

Characteristic snow load on the roof

EN 1991-1-3 · 5.1(3)

s = μi·Ce·Ct·sk,0

s = 0.8 × 1.2 × 1 × 1

s = 0.96 kN/m²

The uniformly distributed load to apply to the roof — multiply by the loaded width to get the line load w (kN/m) on each rafter or beam. For ULS design, combine it with the partial factor γQ from EN 1990.

Try it yourself
06

Wind Load on Roofs

EN 1991-1-4 · Danish NA

Peak velocity pressure, zone-by-zone net uplift and the required steel roof ties — for wind on both the facade and the gable.

qp 0.767 kN/m² · ΣEd facade 19.8 kN

RoofDuo-pitch roof
Building b × l × h10 × 20 × 7 m
Roof pitch30°
Self-weight gk0.6 kN/m²
TerrainII — Low vegetation, isolated obstacles z0 = 0.05 m
Basic wind speed24 m/s

Step-by-step working

01

Terrain category and roughness

EN 1991-1-4 NA.3.1

z0, zmin from the terrain category; kt = 0.19·(z0/0.05)^0.07

z0 = 0.05 m · zmin = 2 m → kt = 0.19·(0.05/0.05)^0.07

kt = 0.19

II — Low vegetation, isolated obstacles. The annex defines five terrain categories with their own roughness lengths.

02

Reference height

EN 1991-1-4 4.3.2

z = max(h, zmin)

h = 7 m · zmin = 2 m

z = 7 m

Below zmin the profile is capped at zmin — the wind speed never drops further.

03

Basic wind velocity and pressure

EN 1991-1-4 4.2

qb = ½·ρ·vb²

vb = 24 m/s · Air density ρ = 1.25 kg/m³ (Danish NA). → 0.5·1.25·24²/1000

qb = 0.36 kN/m²

vb,0 = 24 m/s elsewhere in Denmark.

04

Mean wind speed

EN 1991-1-4 4.3.1

vm = kt·ln(z/z0)·vb

cr = 0.19·ln(7/0.05) = 0.939 → vm = 0.939·24

vm = 22.53 m/s

05

Turbulence intensity

EN 1991-1-4 4.4

Iv = 1/ln(z/z0)

1/ln(7/0.05)

Iv = 0.202

06

Peak velocity pressure

EN 1991-1-4 4.5

qp = (1 + 7·Iv)·½·ρ·vm²

(1 + 7·0.202)·0.5·1.25·22.53²/1000

qp = 0.767 kN/m²

This is the pressure that carries all gusting — used directly for the roof zones.

Characteristic (50-year) wind — cprob = 1.0 in the Danish NA basis.

07

Roof dimensions

roof width = (b + 2f)/cos v · roof length = l + 2g

(10 + 2·0.5)/cos 30° · 20 + 2·0.5

12.7 m × 21 m

Measured on the roof plane — the overhangs belong to the loaded area.

08

Reference distance e

EN 1991-1-4 7.2.2

e = min(b, 2h)

facade: min(20, 2·7) · gable: min(10, 2·7)

e = 14 m (facade) · 10 m (gable)

e sets the width of the edge zones F and G: e/4 strips at the corners, e/10 strips along the edges.

09

Zone forces and roof ties

EN 1991-1-4 7.2.3

Ed = γQ·(cpe + cpi)·qp·A·cos v − γG·gk·A·cos v

γQ = 1.5 · cpi = +0.2 · Anec = Ed·1000/201 → ties = ⌈Anec/60 mm²⌉

cpi = +0.2 · γG = 0.9 · γQ = 1.5

Positive Ed is net uplift. Each zone is anchored with 40 mm × 2 mm steel ties in S235 (Anec = Ed/fyd).

Try it yourself
07

Wind Uplift on a Maltese Roof

EN 1991-1-4 · Maltese annex (indicative)University of Malta — B.Sc. Built Environment Studies

Coursework-style sizing of roof ties for a Mediterranean island dwelling — peak velocity pressure on an exposed coastal site, zone-by-zone net uplift, and the steel ties that hold the roof down. Written for the University of Malta's Built Environment studies.

qp 0.767 kN/m² · ΣEd facade 19.8 kN

RoofDuo-pitch roof
Building b × l × h10 × 20 × 7 m
TerrainII — Low vegetation, isolated obstacles coastal exposure
Basic wind speed24 m/s indicative Maltese site value
Self-weight gk0.6 kN/m²
AnnexMalta select it in the tool

Step-by-step working

01

Terrain category and roughness

EN 1991-1-4 NA.3.1

z0, zmin from the terrain category; kt = 0.19·(z0/0.05)^0.07

z0 = 0.05 m · zmin = 2 m → kt = 0.19·(0.05/0.05)^0.07

kt = 0.19

II — Low vegetation, isolated obstacles. The annex defines five terrain categories with their own roughness lengths.

02

Reference height

EN 1991-1-4 4.3.2

z = max(h, zmin)

h = 7 m · zmin = 2 m

z = 7 m

Below zmin the profile is capped at zmin — the wind speed never drops further.

03

Basic wind velocity and pressure

EN 1991-1-4 4.2

qb = ½·ρ·vb²

vb = 24 m/s · Air density ρ = 1.25 kg/m³ (Danish NA). → 0.5·1.25·24²/1000

qb = 0.36 kN/m²

vb,0 = 24 m/s elsewhere in Denmark.

04

Mean wind speed

EN 1991-1-4 4.3.1

vm = kt·ln(z/z0)·vb

cr = 0.19·ln(7/0.05) = 0.939 → vm = 0.939·24

vm = 22.53 m/s

05

Turbulence intensity

EN 1991-1-4 4.4

Iv = 1/ln(z/z0)

1/ln(7/0.05)

Iv = 0.202

06

Peak velocity pressure

EN 1991-1-4 4.5

qp = (1 + 7·Iv)·½·ρ·vm²

(1 + 7·0.202)·0.5·1.25·22.53²/1000

qp = 0.767 kN/m²

This is the pressure that carries all gusting — used directly for the roof zones.

Characteristic (50-year) wind — cprob = 1.0 in the Danish NA basis.

07

Roof dimensions

roof width = (b + 2f)/cos v · roof length = l + 2g

(10 + 2·0.5)/cos 30° · 20 + 2·0.5

12.7 m × 21 m

Measured on the roof plane — the overhangs belong to the loaded area.

08

Reference distance e

EN 1991-1-4 7.2.2

e = min(b, 2h)

facade: min(20, 2·7) · gable: min(10, 2·7)

e = 14 m (facade) · 10 m (gable)

e sets the width of the edge zones F and G: e/4 strips at the corners, e/10 strips along the edges.

09

Zone forces and roof ties

EN 1991-1-4 7.2.3

Ed = γQ·(cpe + cpi)·qp·A·cos v − γG·gk·A·cos v

γQ = 1.5 · cpi = +0.2 · Anec = Ed·1000/201 → ties = ⌈Anec/60 mm²⌉

cpi = +0.2 · γG = 0.9 · γQ = 1.5

Positive Ed is net uplift. Each zone is anchored with 40 mm × 2 mm steel ties in S235 (Anec = Ed/fyd).

Try it yourself
08

Floor Joists in a Real I-Joist

EN 1995-1-1 · Product-based designVIA (DK) — Architectural Technology & Construction Management

The floor joist method, but with a branded engineered product: a STEICO JSJ-260/45 I-joist, section properties from its flange/web geometry — the Ubakus-style way of designing with a manufacturer's own product instead of sawn timber tables.

ULS OK · SLS OK · u max 5.2 mm

JoistSTEICO JSJ-260/45 · 45x260 mm @ 0.5 m span 4.5 m
Flange qualityC24 service class 1
Usage categoryA1 — rooms in residential buildings qk = 1.5 kN/m²
Acceptable deflectionL/500 9.0 mm
Design effectEd 3.39 kN/m² → 1.70 kN/m on the joist
SourceComputed from 45×45 flange / 10.6 OSB web geometry steico.com

Step-by-step working

01

Permanent loads gk

EN 1991-1-1

Σ gk = covering + joists + insulation + boarding + lining

Floor covering 0.08 + Joists 0.059 + Insulation 0.118 + Sec. spaced boarding 0.016 + Ceiling lining 0.117

Σ gk = 0.39 kN/m²

The joists enter as A·5 kN/m³ ÷ spacing; the insulation fills the joist depth at 0.5 kN/m³.

02

Variable loads qk

EN 1991-1-1 DK NA

qk = imposed load + moveable partitions

category A1 (Rooms in residential buildings): qk = 1.5 · partitions: 0.5

Σ qk = 2 kN/m²

03

Design uniform load and meter load

EN 1990 6.10

Ed = 1.0·gk + 1.5·qk → qjoist = Ed·spacing

1.0·0.39 + 1.5·2 = 3.39 kN/m² · × 0.5 m

Ed = 3.39 kN/m² → 1.7 kN/m on one joist

04

Design forces

Vd = ½·q·L · Md = q·L²/8

Vd = ½·1.7·4.5 · Md = 1.7·4.5²/8

Vd = 3.81 kN · Md = 4.29 kNm

05

Design bending strength

EN 1995-1-1 2.4.1

fmd, fvd from the quality and service class tables

C24 · service class 1 (Moisture ≤ 12 % — indoor.)

fmd = 14.2 N/mm² · fvd = 1.5 N/mm²

06

Bending check — ULS

EN 1995-1-1 6.1.6

Wness = Md/fmd ≤ Wy

4.29·1000/14.2 = 302 ·×10³ mm³ vs 399 ·×10³ mm³

OK — 399 ≥ 302 ×10³ mm³

07

Shear check — ULS

EN 1995-1-1 6.1.7

σvd = 1.5·Vd/A ≤ fvd

1.5·3.81·1000/5852 = 0.978 N/mm² vs fvd = 1.5

OK — 0.978 ≤ 1.5 N/mm²

08

Instantaneous and final deflection — SLS

EN 1995-1-1 7.2

uinst = 5·q·L⁴/(384·E·Iy) · ufin = uinst·(1 + ψ2·kdef)

frequent: 0.5 kN/m → 4.64 → 5.19 mm · quasi-perm.: 0.4 kN/m → 3.7 → 4.15 mm

governing u = 5.19 mm

E = 11000 N/mm², Iy = 51826·10³ mm⁴, kdef = 0.6 (class 1), ψ2 = 0.2.

09

Deflection limit

limit = L/500 (rounded up)

4.5·1000/500

OK — 9.0 mm ≥ 5.19 mm

Try it yourself

ArchiStructura — Eurocode Student Toolkit

Based on EN 1990, EN 1991, EN 1992-1-1, EN 1993-1-1, EN 1995-1-1 & EN 1997-1.
Educational tool only — always verify against the National Annex and a qualified engineer. The full Eurocodes are published by your national standards body.